Uniform Building Codes and Compliances
Prior to planning, Interior Designer will evaluate the given building to check for codes compliance. This is usually as part of the building feasibility study to examine if the given building facilities are appropriate to accommodate the client's needs and operations.
The discussion here will concentrate on the Uniform building Codes that planners use in the evaluation of building.
Types of codes to consider in Pre-planning
Egress Requirements
Factors to consider in Planning for egress
- Types of construction
- Types of occupancy
- Occupancy factor and occupancy load
Types of Construction and Occupancy
Most corporate offices are high rises that are classifed uner Type I or type II construction. Office is classified as Business under the Occupancy type. If there are other needs such as assembly, laboratories, etc. will be classifed as Mixed Occupancy type.
Occupancy factor and Occupancy Load
The occupancy factors is used to calculate the occupancy load:
- Assembly of concentrated use is 7 sq ft net (auditoriums, churches, stadiums)
- Assembly of less concentrated use is 15 sq ft net (conferences, exhibits, lounges, etc)
- Business such as offices, banks, etc. is 100 sq ft gross
Notes:
The net areas do not include corridors, restrooms, mechanical rooms, utility closets, stairs, etc.
In the case of mixed use, the occupancy load of the floor is equal to the sum of the occupancy load of each type of occupancy.
Number of Exits
The total number of exits is determined by the occupancy load but the minimum is 2 exits whether they are for a whole building, or a typical floor or a space within the building. Occupancy load of a floor is determined by total square feet of that floor divide by the occupancy factor based on the types of occupancy. If the occupants exit through that floor, the calculation must add 50% of the floor directly above or below, and 25% of all other floors beyond served by that floor. The total number of exits required are:
- 1-500 will be 2 exits
- 500-1000 will be 3 exits
- 0ver 1000 will be 4 exits
Note: The floor with the largest occupant load determines the number of required exits for all lower floors. If there is mixed occupancies, then the occupancy load is tabulated by calculating each occupancy type separately and then adding them together.
Arrangement of Exit
Distance between the stairwells should be no less than 50% of the longest distance between two point of the building. This is usually the diagonal of the building. It is measured using a straight line between the center of doot to center of door between the two exits. If this failied the requirements, then use a rated corridor to connect the two stairwells and the distance will be measured from the center of one exit to the center of the next exit travel along the center of the corridor.
Travel Distance
Exit maximum travel distance for Business and Assembly occupancies is 200 feet for non-sprinkler space and 250 feet for sprinkler space. This is measure from the most remote location in the building and travel along the isles and corridor until the stariwell door is reached.
The codes allow additional 100 feet to reach the exits if the last portion of the travel distance is within a one hour rated corridor.
No dead ends shall be more than 20 feet long.
Occupancy Separation
Separation is needed between different occupancy types or between different uses of the same type of occupancy. Occupancy types occupancy separation
- Large or small assembly - 2 hours
- Business - 1 hour
- Educational - 2 hour
- Hazardous check codes of different types
- Merchantile - 1 hour
- Storage, moderate hazard - 3 hours
- Storage, low hazard - 2 hours
- residential - 1 hour
- Institutional - 2 hours
Rated corridors is required if there are more than 1 tenant on the same floor. Rated corridor or exit access corridor has a minimum fire rating 1 hour including surrounding partitions and ceiling.
Walls enclosing exit stairs have 1 hour rating for buildings with 3 stories or less and 2 hour rating if they are four or more stories.
Boiler rooms, furnace rooms and large storage rooms or hazardous material storage rooms require 1 hour to 2 hours separations from the rest of the building.
Storage rooms more than 50 sq ft and less than 100 sq ft requires 1 hour rating otherwise 2 hours.
The walls forming the means of egress must have 3 hours fire rating and self-closing exit doors must have 1 hour rating.